Electrical Inspector One- and Two-Family Dwellings (2A) Exam Prep
Free practice questions

Free 2A Practice Questions

10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.

Start the free practice test → ★★★★★4.9/5 from 2,400+ candidates · No signup

The 2A exam has 50 questions and runs 2 hours.

These 10 free 2A questions are organized by exam domain, so you can see how each part of the Electrical Inspector One- and Two-Family Dwellings (2A) blueprint is tested. Reveal the answer and explanation under each question.

Domain 1: Cabinets, Panelboards, Switchboards, Boxes, and Conduit Bodies

Question 1

On a garage plan, a 20-inch-wide, 120/240-volt single-phase panel sits beside an interior partition. Its unobstructed working space spans the full cabinet width and extends 12 inches farther to the right: 32 inches wide, 40 inches deep from the cabinet front, and 80 inches high from the floor. The panel top is 72 inches above the floor; its door opens 100 degrees. Using the 2020 NEC, which plan-review comment on these dimensions is justified?

Show answer & explanation

Correct answer: D - The working-space dimensions comply; centering the panel is unnecessary.

Domain 2: Calculations of Load

Question 2

For a one-family dwelling with a single 120/240 V service, an NEC 2020 optional-method worksheet has a general-load subtotal of 34,000 VA before demand factors. This includes every applicable load except the heat-pump compressor and supplemental resistance heat. The heat-pump compressor is rated 4,800 VA; its 12,000 VA supplemental resistance heat can operate simultaneously with it. There is no other heating or cooling equipment. Apply 100% to the first 10,000 VA of general load and 40% to the remainder. After including the applicable HVAC demand, which is the smallest standard service rating that meets the load?

Show answer & explanation

Correct answer: B - 150 A

Domain 4: Conductors and Overcurrent Protection on the Load Side of the Service

Question 3

Lights on one leg of a dwelling's multiwire branch circuit dim while lights on the other leg brighten. An electrician records 78 V and 162 V from the two ungrounded conductors to the shared neutral at a downstream junction box, with both load groups connected. Line-to-line voltage there is 240 V; both line-to-neutral readings at the supplying panel remain 120 V. Which defect best explains all of these findings?

Show answer & explanation

Correct answer: C - An open or high-resistance shared-neutral connection between the panel and loads.

Domain 5: Lighting and Utilization Equipment

Question 4

The nameplate on a dwelling's listed multimotor air-conditioning unit states a minimum circuit ampacity of 26.4 A and a maximum fuse or circuit-breaker rating of 45 A. Its conductors have a final allowable ampacity of 30 A after all applicable limitations, and a 40-A circuit breaker supplies the unit without starting problems. How should the inspector assess these two ratings under the 2020 NEC?

Show answer & explanation

Correct answer: A - Both installed ratings meet the marked MCA and maximum breaker limit.

Question 5

Replacing an enclosed recessed LED luminaire with an enclosed surface-mounted LED would leave the new fixture on a closet ceiling, 9 inches from the nearest point of the code-defined storage space. The recessed fixture also has 9 inches of clearance. The proposed fixture is not identified for installation within closet storage space. Under the 2020 NEC, how does this substitution affect compliance?

Show answer & explanation

Correct answer: A - Only the surface-mounted replacement fails the required storage-space clearance.

Domain 6: Service Equipment and Conductors on the Supply Side of the Service

Question 6

An exterior nonfused switch marked "EMERGENCY DISCONNECT, NOT SERVICE EQUIPMENT" has been added ahead of a dwelling's indoor service main. The indoor main remains the service disconnect, and the exterior enclosure is properly bonded. Under the 2020 NEC, what must be done with the indoor main bonding jumper?

Show answer & explanation

Correct answer: A - Keep the main bonding jumper at the indoor service disconnect.

Question 7

A fall-of-potential test documents 18 ohms to earth for a dwelling service's only grounding electrode: a properly installed, listed rod with 8 feet of soil contact. No other qualifying electrodes are present. Under the 2020 NEC, how does this result affect the electrode requirement?

Show answer & explanation

Correct answer: B - The rod meets the exception permitting a single electrode.

Domain 7: Special Installations or Constructions

Question 8

A stainless-steel ladder at a new permanently installed pool is connected to a separate ground rod measuring 12 ohms to earth. The ladder is attached to the pool structure but has no connection to its equipotential bonding system. The pump's equipment grounding conductor is intact, and its GFCI operates properly. Applying the 2020 NEC pool requirements, which inspection decision is justified for the ladder?

Show answer & explanation

Correct answer: D - Connect the metal ladder to the existing pool equipotential bonding system.

Domain 9: Wiring Methods

Question 9

The conductors in a buried PVC feeder raceway are dual-marked "THHN/THWN-2." The installer credits the sealed raceway ends for making them acceptable; sizing and fill are correct. Under the 2020 NEC, which assessment correctly addresses their location suitability?

Show answer & explanation

Correct answer: D - Their THWN-2 marking makes them suitable for the wet location.

Question 10

Fourteen inches of cover separates the top of a direct-buried UF-B cable from finished grade where it crosses a private driveway used only for a one-family dwelling. The cable supplies driveway lights on a 120 V, 20 A branch circuit protected by GFCI at its origin. Apply Table 300.5 of the 2020 NEC to evaluate the measured cover.

Show answer & explanation

Correct answer: B - The 14-inch cover satisfies the requirement for this circuit and location.